Compact S
Specifications & Technical Data
Compact S is an energy-efficient total indoor climate solution for all types of low-energy buildings, single-family homes, flats and small office areas in commercial leases with a ventilation requirement of up to 375 m3/h.
The heat pump has a reversible cooling circuit, which means that, in the summer, the unit can cool the supply air by up to 10 °C. Due to the low air exchange, the cooling does not function as an air conditioning system. On cooling, the supply air is dehumidified, which gives a more pleasant indoor climate than is possible with an ordinary ventilation unit without a heat pump.
			ECODESIGN
| Consumer profile, water heater | L (large) | 
| Energy efficiency class | A | 
| Energy efficiency for water heating – average climate | 118 % | 
| Annual electricity consumption – average climate | 852 kWh/annum | 
| Temperature settings on the thermostat | 10 – 65 °C | 
| Sound power level LWA | 57 dB(A) | 
| The water heater can function outside peak load periods (Smart-grid) | No | 
| Guidelines for assembly, installation and maintenance | See installation instructions | 
| Energy efficiency for water heating – cold climate | 118 % | 
| Energy efficiency for water heating – warm climate | 118 % | 
| Annual electricity production – cold climate | 852 kWh/annum | 
| Annual electricity consumption – warm climate | 852 kWh/annum | 
			TECHNICAL DATA
| Dimensions (WxDxH) | 600 x 600 x 2250 mm | 
| Weight | 160 kg | 
| Plate type casing | Aluzinc steel plate, white powder coating RAL9016 | 
| Heat exchanger type | Polystyrene counterflow heat exchanger | 
| Fan type | EC, constant rotation | 
| Filter class | Standard G4 | 
| Duct connections | Ø 160 mm | 
| Condensate drain | PVC, Ø 20×1,5 mm | 
| External leakage | < 0,78% | 
| Internal leakage | < 1,47% | 
| Supply voltage | 230 V (±10 %), 50/60 HZ | 
| Tightness class | IP31 | 
| Standby power | 3 W | 
| Ambient temperature | -20/+40 °C | 
| Refrigerant | R134a | 
Ecodesign/ERP data
| Fan data | |
| Motordata (optimalt driftspunkt) | 
* 1 Input without heating element (accessory).
* 2 Input Compact Polar
* 3 At ± 250 Pa and 265 m3/h according EN 13141-7.
* 4 At ± 100 Pa and 265 m3/h according EN 13141-7.
			1: Fresh air
2: Supply air
3: Extract air
4: Discharge air
			AUTOMATION
			The CTS602 comes with factory settings, including a default setting which can be customised to operational requirements to achieve optimum operation and utilisation of the system.
The operating panel must be placed in a dry, frost-free location, at least 1.5 m above floor level and at least 0.5 m from any corner. Avoid placing the panel on an external wall or in areas in direct sunlight.
Operating instructions for the CTS 602 can be found in a separate user manual supplied with the unit.
Functional overview CTS 602
CLICK TO VIEW
| Functional overview | 
 + Standard – Accessories  | 
|
| 3 levels | The control function is divided into 3 levels: User/Service/Factory with various options at each level | + | 
| Weekly plan | The unit has 3 weekly programmes (with a factory setting of “off”) • Programme 1: for working families • Programme 2: for stay-at-home families • Programme 3: for businesses There is also an option for you to set your own weekly programme.  | 
+ | 
| User option 1 | This allows you to override the operating mode in the main menu via an external potential-free contact or PIR sensor. | + | 
| User option 2 | With an Expansion PCB mounted, allows you to make additional connections, e.g. • User option 2 overrides User option 1 (e.g. connecting an EM box) • Up to 500 W direct • Output relai • Switching the central heating system on/off  | 
|
| Alarms | Alarm log featuring the last 16 alarms. | + | 
| Filter monitor | Filter monitor with timer (factory setting of 90 days). Adjustable to 30/90/180/360 days. | + | 
| 
 Bypass  | 
Bypassing the outdoor air reduces heat recovery, enabling the desired supply air temperature to be maintained spring, summer and autumn. | + | 
| Air quality | Allows you to choose whether to switch humidity sensors and/or CO2 sensors on and off. | +/- | 
| Humidity control | Allows you to set a higher or lower ventilation step in the case of high/low air humidity. | + | 
| Summer/Winter operation | Possible to set operation for summer and vinter | |
| Winter low | Allows you to select a low ventilation step in the case of low outside temperatures | |
| Defrost function | Temperature-based automatic function for defrosting the heat exchanger. | + | 
| Frost protection | In case of failing heating system, the unit is turned off to avoid further cooling with a risk of the water heating coil frost bursting. | + | 
| Temperature control | Allows you to select the temperature sensor which will control the unit. • T15 ROOM (panel sensor) • T10 EXT (fitted in a representative extraction valve) • T3 EXHAUST (extract air)  | 
+ | 
| Room low | Stops the unit at a low room temperature. Hereby is cooling of the home avoided in case of a failing central heating system. Standard set to OFF. Can be set from 1 to 20 degrees and is controlled by: • T15 ROOM (panel sensor) • T10 EXT (fitted in a representative extraction valve) • T3 EXHAUST (extract air)  | 
+ | 
| Air volume | Allows you to set four ventilation steps. Supply air and extract air are set individually. • Step 1 < 25% – Step 2 < 45% – Step 3 < 70% – Step 4 < 100%  | 
+ | 
| Legionella control | It is possible to choose a weekday or a day during the month, where the sanitary hot water temperature reaches 65 °C, for example between 1 and 6 o´clock.  | 
|
| External firealarm | Possible to connect the unit to external firealarm. | |
| Joint alarm | Outlet for joint alarm. | + | 
| Constant pressure control | Allows control from both the extract air and supply air side. | – | 
| Cooling | Via bypass (can only cool with outdoor temperature) and cool recovery (can only cool with indoor temperature). This allows you to choose whether to run the system at a higher or the highest ventilation step during cooling. The weekly programme has an option for setting cooling at night.  | 
+ | 
| Intake air control | Allows you to set the regulator to control the intake air temperature/supply air (only available if the control unit has been configured for a supply-heating element).  | 
+ | 
| External heating element | • Temperature sensor T7 is an supply air sensor • Integrated frost protection for external water heating element • Motorised valve and circulation pump control unit  | 
+ | 
| External electric heating element | • Temperature sensor T7 is an supply air sensor • Overheating protection  | 
– | 
| Delayed start-up | There is a possibility for a delayed start-up by the fans, when a closing damper is installed. | + | 
| Reset | Allows you to restore the factory settings. | + | 
| Manual test | Allows you to test the unit’s functions manually. | + | 
| Language | Option for setting the relevant language (Danish/Finnish/Norwegian/Swedish/German/English/French). | + |